Conductor: Compact stranded hard drawn Aluminium Conductor ( Class2)
Conductor shield: Semi-conducting cross-linked polyethylene.
Insulation: Cross-linked polyethylene (Natural)
Sheath: Track resistant cross-linked polyethylene (Black)
Package : Export wooden drum & iron wooden drum or as customer require
Email:uvlead@aliyun.com
Email:tlfast@aliyun.com
This standard applies of supported spacer cable. These conductors are intended primarily for the distribution of electrical energy under normal conditions of overhead (aerial) installations. They are considered as covered conductors therefore the cables carry no voltage rating. The conductors must be installed on insulators and/or spacers adequate for the service voltage. The user may want to give consideration to the dielectric compatibility of the covering, insulator, spacer.
The conductors are stranded,circular compressed aluminum. The conductor screen is the extruded Semi-conducting conductor shield in Black. The inner Insulation is mainly natural color thermoplastic polyethylene (PE) or cross-linked polyethylene (XLPE). And the outer Insulation is mainly thermoplastic polyethylene (PE) or cross-linked polyethylene (XLPE) in Black or Grey with Weather or UV resistant. This standard covers both thermoplastic and cross linked polyethylene constructions, rated for 75°C or 90°C normal service temperature.
15kV SAC Cable
| Nominal Size | Min. No. of Wires | Covering Thickness | Cable Diameter | Min. Breaking Load | Weight | ||||
| Conductor Shield | Inner Layer | Outer Layer | |||||||
| mm² | No. | mm | mm | mm | mm | N | kg/km | ||
| 3-Layer 15kV AAC/XLPE/HDPE | |||||||||
| 25 | 6 | 0.60 | 1.91 | 1.91 | 15.2 | 3762 | 221 | ||
| 35 | 6 | 0.60 | 1.91 | 1.91 | 16.2 | 5177 | 261 | ||
| 50 | 6 | 0.60 | 1.91 | 1.91 | 17.3 | 7011 | 310 | ||
| 70 | 12 | 0.60 | 1.91 | 1.91 | 19.0 | 10354 | 390 | ||
| 95 | 15 | 0.60 | 1.91 | 1.91 | 20.8 | 13727 | 486 | ||
| 120 | 15 | 0.60 | 1.91 | 1.91 | 22.0 | 17339 | 568 | ||
| 150 | 15 | 0.60 | 1.91 | 1.91 | 23.7 | 21033 | 664 | ||
| 185 | 30 | 0.60 | 1.91 | 1.91 | 25.3 | 26732 | 785 | ||
| 240 | 30 | 0.60 | 1.91 | 1.91 | 27.6 | 34679 | 973 | ||
25kV SAC Cable
| Nominal Size | Min. No. of Wires | Covering Thickness | Cable Diameter | Min. Breaking Load | Weight | ||
| Conductor Shield | Inner Layer | Outer Layer | |||||
| mm² | No. | mm | mm | mm | mm | N | kg/km |
| 3-Layer 25kV AAC/XLPE/HDPE | |||||||
| 25 | 6 | 0.70 | 3.18 | 3.18 | 20.1 | 3762 | 356 |
| 35 | 6 | 0.70 | 3.18 | 3.18 | 21.1 | 5177 | 404 |
| 50 | 6 | 0.70 | 3.18 | 3.18 | 22.2 | 7011 | 461 |
| 70 | 12 | 0.70 | 3.18 | 3.18 | 23.9 | 10354 | 555 |
| 95 | 15 | 0.70 | 3.18 | 3.18 | 25.7 | 13727 | 664 |
| 120 | 15 | 0.70 | 3.18 | 3.18 | 26.9 | 17339 | 755 |
| 150 | 15 | 0.70 | 3.18 | 3.18 | 28.6 | 21033 | 864 |
| 185 | 30 | 0.70 | 3.18 | 3.18 | 30.2 | 26732 | 997 |
| 240 | 30 | 0.70 | 3.18 | 3.18 | 32.5 | 34679 | 1203 |
| Nominal Size | Min. No. of Wires | Covering Thickness | Cable Diameter | Min. Breaking Load | Weight | ||
| Conductor Shield | Inner Layer | Outer Layer | |||||
| mm² | No. | mm | mm | mm | mm | N | kg/km |
| 3-Layer 35kV AAC/XLPE/HDPE | |||||||
| 25 | 6 | 0.70 | 4.45 | 3.18 | 22.6 | 3762 | 439 |
| 35 | 6 | 0.70 | 4.45 | 3.18 | 23.6 | 5177 | 491 |
| 50 | 6 | 0.70 | 4.45 | 3.18 | 24.7 | 7011 | 552 |
| 70 | 12 | 0.70 | 4.45 | 3.18 | 26.4 | 10354 | 652 |
| 95 | 15 | 0.70 | 4.45 | 3.18 | 28.2 | 13727 | 768 |
| 120 | 15 | 0.70 | 4.45 | 3.18 | 29.4 | 17339 | 864 |
| 150 | 15 | 0.70 | 4.45 | 3.18 | 31.1 | 21033 | 980 |
| 185 | 30 | 0.70 | 4.45 | 3.18 | 32.7 | 26732 | 1119 |
| 240 | 30 | 0.70 | 4.45 | 3.18 | 35.0 | 34679 | 1334 |