Send message
+86 186 3119 9200
uvlead@aliyun.com
8618631199200
NAYY Cable

0.6/1kV Aluminum Conductor Low Voltage Power Cable with PVC Insulation and Sheath AL-PVC-PVC

Conductor: Aluminum

Insulation: PVC

Sheath: PVC

Voltage : 0.6/1kV

Number of cores: Multi Core

Package : Export wooden drum & iron wooden drum or as customer require

Email:uvlead@aliyun.com

Email:tlfast@aliyun.com

 NAYY Cable Application:

NAYY cable is suitable for fixed installations, preferably in cable ducts, indoors, outdoors, in water or underground if no mechanical damage is to be expected.

NAYY Cable Standards:

 

DIN VDE 0276-603 HD 603 S1 DIN EN 60228 class 1 and 2 (construction) HD 308 S2 (core identification) 


CONSTRUCTION :

NAYY Cable Construction:


1. Conductor: Copper or aluminum, Class 1: solid conductor, or Class 2: stranded conductor
2. Insulation: Polyvinyl chloride PVC
3. Outer sheath: Polyvinyl chloride PVC 


TECHNICAL DATA :

Voltage Rating Uo/U (Um) 0.6/1 (1.2)kV
Nominal Voltage DC (core-earth/core-core) :1.8/1.8kV
Test Voltage:4kV

Temperature Rating:
Flexed: 5°C to +70°C
Fixed: -35°C to +70°C

Maximum Short Circuit Temperature:

+160°C (max 5 seconds)

Minimum Bend Radius:
Single core: 15 x overall diameter
Multi core: 12 x overall diameter 


PARAMETER :
0.6/1kV-1 core aluminum conductor PVC insulated PVC sheathed power cable
No. of cores and nominal cross sectionThickness of Insulation Thickness of SheathApprox. overall DiameterApprox. weightMax. DC resistance of conductor(20℃)Current carrying capacity
(mm2)(mm)(mm)(mm)(kg/km)(Ω/km)In Air(A)In Ground(A)
1X101.01.48.6973.084265
1X161.01.49.61251.915885
1X251.21.411.21711.274105
1X351.21.412.22060.86890125
1X501.41.413.62650.641110150
1X701.41.415.53430.443140185
1X951.61.517.74530.32170225
1X1201.61.519.15450.253200255
1X1501.81.6216750.206230285
1X1852.01.723.38210.164265323
1X2402.21.826.210440.125320380
1X3002.41.92912840.1370430
1X4002.6232.316380.0778435490
1X5002.82.136.220630.0605510565
1X6302.82.24025150.0469600655
0.6/1kV-2 core aluminum conductor PVC insulated PVC sheathed power cable
No. of cores and nominal cross sectionThickness of Insulation Thickness of SheathApprox. overall DiameterApprox. weightMax. DC resistance of conductor(20℃)Current carrying capacity
(mm2)(mm)(mm)(mm)(kg/km)(Ω/km)In Air(A)In Ground(A)
2X2.50.81.810.911812.119-
2X411.812.71567.4126-
2X611.813.71854.6134-
2X1011.816.22553.084465
2X1611.818.43301.915985
2X251.21.821.74541.276110
2X351.21.823.05380.86893135
2X501.41.826.46990.641115160
2X701.41.929.78990.443145195
2X951.62.034.211960.32170235
2X1201.62.137.214360.253205270
2X1501.82.241.217760.206235305
2X18522.445.521650.164275345
0.6/1kV-3 core aluminum conductor PVC insulated PVC sheathed power cable
No. of cores and nominal cross sectionThickness of Insulation Thickness of SheathApprox. overall DiameterApprox. weightMax. DC resistance of conductor(20℃)Current carrying capacity
(mm2)(mm)(mm)(mm)(kg/km)(Ω/km)In Air(A)In Ground(A)
3X2.50.81.811.413712.117-
3X41.01.813.31887.4122-
3X61.01.814.52244.6129-
3X101.01.817.13073.083855
3X161.01.819.54031.915173
3X251.21.823.15591.26594
3X351.21.824.56730.86880110
3X501.41.828.28820.64198135
3X701.41.931.811500.443120165
3X951.62.136.615380.32150200
3X1201.62.239.918550.253180230
3X1501.82.344.223010.206200255
3X18522.548.828100.164235290
3X2402.22.755.035970.125280335
3X3002.42.860.844280.1320375
0.6/1kV-4 core aluminum conductor PVC insulated PVC sheathed power cable
No. of cores and nominal cross sectionThickness of Insulation Thickness of SheathApprox. overall DiameterApprox. weightMax. DC resistance of conductor(20℃)Current carrying capacity
(mm2)(mm)(mm)(mm)(kg/km)(Ω/km)In Air(A)In Ground(A)
4X2.50.81.812.316012.117-
4X411.814.42247.4122-
4X611.815.72704.6129-
4X1011.818.73733.083855
4X1611.821.34941.915173
4X251.21.825.36921.26594
4X351.21.826.98380.86880110
4X501.41.931.211180.64198135
4X701.42.035.314640.443120165
4X951.62.240.719620.32150200
4X1201.62.344.323710.253180230
4X1501.82.549.229460.206200255
4X18522.654.436030.164235290
4X2402.22.961.346190.125280335
4X3002.43.167.856940.1320375
0.6/1kV-5 core aluminum conductor PVC insulated PVC sheathed power cable
No. of cores and nominal cross sectionThickness of Insulation Thickness of SheathApprox. overall DiameterApprox. weightMax. DC resistance of conductor(20℃)Current carrying capacity
(mm2)(mm)(mm)(mm)(kg/km)(Ω/km)In Air(A)In Ground(A)
5X2.50.81.813.3195.812.122-
5X411.815.6271.37.4129-
5X611.817.1320.44.6138-
5X1011.820.4455.33.085155
5X1611.823.4593.71.916573
5X251.21.827.9837.11.28094
5X351.21.929.71026.10.86898110
5X501.42.034.61377.50.641120135
5X701.42.239.21806.40.443150165
5X951.62.345.22425.60.32180200
5X1201.62.549.32934.60.253200230
5X1501.82.654.83650.90.206235255
5X18522.860.54468.00.164280290
5X2402.23.168.35734.50.125320335
5X3002.43.375.57074.10.1380375
0.6/1kV-3+1 core aluminum conductor PVC insulated PVC sheathed power cable
No. of cores and nominal cross sectionThickness of Insulation Thickness of SheathApprox. overall DiameterApprox. weightMax. DC resistance of conductor(20℃)Current carrying capacity
(mm2)(mm)(mm)(mm)(kg/km)(Ω/km)In Air(A)In Ground(A)
3*4+1*2.51.0/0.81.813.92177.41/12.129-
3*6+1*41.0/1.01.815.42594.61/7.4138-
3*10+1*61.0/1.01.818.03473.08/4.615155
3*16+1*101.0/1.01.820.74641.91/3.086573
3*25+1*161.2/1.01.824.46591.2/1.918094
3*35+1*161.2/1.01.825.67640.868/1.9198110
3*50+1*251.4/1.21.929.810250.641/1.2120135
3*70+1*351.4/1.22.033.313230.443/0.868150165
3*95+1*501.6/1.42.138.417650.32/0.641180200
3*120+1*701.6/1.42.242.221450.253/0.443200230
3*150+1*701.8/1.42.445.925370.206/0.443235255
3*185+1*952.0/1.62.551.032070.164/0.32280290
3*240+1*1202.2/1.62.757.240330.125/0.253320335
3*300+1*1502.4/1.82.963.349800.1/0.206380375
0.6/1kV-4+1core aluminum conductor PVC insulated PVC sheathed power cable
No. of cores and nominal cross sectionThickness of Insulation Thickness of SheathApprox. overall DiameterApprox. weightMax. DC resistance of conductor(20℃)Current carrying capacity
(mm2)(mm)(mm)(mm)(kg/km)(Ω/km)In Air(A)In Ground(A)
4*4+1*2.51.0/0.81.815.22497.41/12.129-
4*6+1*41.0/1.01.816.83094.61/7.4138-
4*10+1*61.0/1.01.819.74203.08/4.615155
4*16+1*101.0/1.01.822.85631.91/3.086573
4*25+1*161.2/1.01.827.07921.2/1.918094
4*35+1*161.2/1.01.828.49320.868/1.9198110
4*50+1*251.4/1.22.033.212820.641/1.2120135
4*70+1*351.4/1.22.137.316480.443/0.868150165
4*95+1*501.6/1.42.343.122450.32/0.641180200
4*120+1*701.6/1.42.447.327310.253/0.443200230
4*150+1*701.8/1.42.551.632290.206/0.443235255
4*185+1*952.0/1.62.757.540420.164/0.32280290
4*240+1*1202.2/1.63.064.551430.125/0.253320335
4*300+1*1502.4/1.83.271.463420.1/0.206380375
0.6/1kV-3+2 core aluminum conductor PVC insulated PVC sheathed power cable
No. of cores and nominal cross sectionThickness of Insulation Thickness of SheathApprox. overall DiameterApprox. weightMax. DC resistance of conductor(20℃)Current carrying capacity
(mm2)(mm)(mm)(mm)(kg/km)(Ω/km)In Air(A)In Ground(A)
3*4+2*2.51.0/0.81.814.72347.41/12.129-
3*6+2*41.0/1.01.816.52984.61/7.4138-
3*10+2*61.0/1.01.819.03943.08/4.615155
3*16+2*101.0/1.01.822.25331.91/3.086573
3*25+2*161.2/1.01.826.07391.2/1.918094
3*35+2*161.2/1.01.827.08410.868/1.9198110
3*50+2*251.4/1.21.932.012120.641/1.2120135
3*70+2*351.4/1.22.035.414860.443/0.868150165
3*95+2*501.6/1.42.241.020040.32/0.641180200
3*120+2*701.6/1.42.345.324770.253/0.443200230
3*150+2*701.8/1.42.448.528590.206/0.443235255
3*185+2*952.0/1.62.654.436280.164/0.32280290
3*240+2*1202.2/1.62.860.745700.125/0.253320335
3*300+2*1502.4/1.83.067.256240.1/0.206380375
Related products